Permit Number: TC-COM-0325-00427
Parcel: 140420760

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0325-00427
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2025 Site Zoning Standard APPROVED
03/27/2025 Water - PDSD Standard APPROVED
04/01/2025 Site Engineering Standard NOT REQUIRED
04/01/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/19/2025 Commercial Building Standard REQUIRES RESUBMIT March 19, 2025
1st Review

Seaver Franks
Attn: Nurlan Herburger
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: CORD BLOOD REGISTRY – DEWAR
ADDITION AND TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0325-00427
Stantec Project Number: 185215066
Stantec File Number: TUC-25-033

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B III-B 36,747 286 Yes Yes
S-2 41,250
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Earthwork, concrete, epoxy anchors, field welding, and masonry.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and fire alarm system [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal). Currently Sheet A0.0 indicates these items as a deferred submittal.

Sheets A2.0 and A6.0

1. New Stairwell 120-6 requires on the first floor a reduced vertical clearance rail or other form of barrier at the stair per ICC/ANSI A117.1-2009 Sec. 307.4. Any area under the stair that has a vertical clearance less than 80” needs to have a rail with a leading edge located 27” maximum above the floor, or some other form of barrier.

Sheet A2.1

1. The guard is missing in Stairwell 120-6 at the upper landing. There needs to be a 42” high guard at the second-floor landing per 2018 IBC Sec. 1015.

Sheet A7.0

1. Detail 6 is titled as a “handrail”; however the rail is too tall for a handrail. This detail is likely a “guard” and as such its overall height need to be 42” per 2018 IBC Sec. 1015.3; however this dimension is not indicated on the detail. {Detail 7 has a similar issue; what is the height of the guard above the leading edge of the tread?}

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

Sheet M2.0

1. The COMcheck is missing from this sheet. There is a “box” labeled COMcheck on the sheet, however the box is empty.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.



Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Joel Svoboda, RA
Senior Associate
520-545-7415
joel.svoboda@stantec.com
03/19/2025 Commercial Electrical Standard REQUIRES RESUBMIT March 19, 2025
1st Review

Seaver Franks
Attn: Nurlan Herburger
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: CORD BLOOD REGISTRY – DEWAR
ADDITION AND TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0325-00427
Stantec Project Number: 185215066
Stantec File Number: TUC-25-033

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B III-B 36,747 286 Yes Yes
S-2 41,250
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Earthwork, concrete, epoxy anchors, field welding, and masonry.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and fire alarm system [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal). Currently Sheet A0.0 indicates these items as a deferred submittal.

Sheets A2.0 and A6.0

1. New Stairwell 120-6 requires on the first floor a reduced vertical clearance rail or other form of barrier at the stair per ICC/ANSI A117.1-2009 Sec. 307.4. Any area under the stair that has a vertical clearance less than 80” needs to have a rail with a leading edge located 27” maximum above the floor, or some other form of barrier.

Sheet A2.1

1. The guard is missing in Stairwell 120-6 at the upper landing. There needs to be a 42” high guard at the second-floor landing per 2018 IBC Sec. 1015.

Sheet A7.0

1. Detail 6 is titled as a “handrail”; however the rail is too tall for a handrail. This detail is likely a “guard” and as such its overall height need to be 42” per 2018 IBC Sec. 1015.3; however this dimension is not indicated on the detail. {Detail 7 has a similar issue; what is the height of the guard above the leading edge of the tread?}

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

Sheet M2.0

1. The COMcheck is missing from this sheet. There is a “box” labeled COMcheck on the sheet, however the box is empty.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.



Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Joel Svoboda, RA
Senior Associate
520-545-7415
joel.svoboda@stantec.com
03/19/2025 Commercial Mechanical Standard REQUIRES RESUBMIT March 19, 2025
1st Review

Seaver Franks
Attn: Nurlan Herburger
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: CORD BLOOD REGISTRY – DEWAR
ADDITION AND TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0325-00427
Stantec Project Number: 185215066
Stantec File Number: TUC-25-033

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B III-B 36,747 286 Yes Yes
S-2 41,250
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Earthwork, concrete, epoxy anchors, field welding, and masonry.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and fire alarm system [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal). Currently Sheet A0.0 indicates these items as a deferred submittal.

Sheets A2.0 and A6.0

1. New Stairwell 120-6 requires on the first floor a reduced vertical clearance rail or other form of barrier at the stair per ICC/ANSI A117.1-2009 Sec. 307.4. Any area under the stair that has a vertical clearance less than 80” needs to have a rail with a leading edge located 27” maximum above the floor, or some other form of barrier.

Sheet A2.1

1. The guard is missing in Stairwell 120-6 at the upper landing. There needs to be a 42” high guard at the second-floor landing per 2018 IBC Sec. 1015.

Sheet A7.0

1. Detail 6 is titled as a “handrail”; however the rail is too tall for a handrail. This detail is likely a “guard” and as such its overall height need to be 42” per 2018 IBC Sec. 1015.3; however this dimension is not indicated on the detail. {Detail 7 has a similar issue; what is the height of the guard above the leading edge of the tread?}

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

Sheet M2.0

1. The COMcheck is missing from this sheet. There is a “box” labeled COMcheck on the sheet, however the box is empty.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.



Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Joel Svoboda, RA
Senior Associate
520-545-7415
joel.svoboda@stantec.com
03/19/2025 Commercial Plumbing Standard REQUIRES RESUBMIT March 19, 2025
1st Review

Seaver Franks
Attn: Nurlan Herburger
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: CORD BLOOD REGISTRY – DEWAR
ADDITION AND TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0325-00427
Stantec Project Number: 185215066
Stantec File Number: TUC-25-033

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B III-B 36,747 286 Yes Yes
S-2 41,250
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Earthwork, concrete, epoxy anchors, field welding, and masonry.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and fire alarm system [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal). Currently Sheet A0.0 indicates these items as a deferred submittal.

Sheets A2.0 and A6.0

1. New Stairwell 120-6 requires on the first floor a reduced vertical clearance rail or other form of barrier at the stair per ICC/ANSI A117.1-2009 Sec. 307.4. Any area under the stair that has a vertical clearance less than 80” needs to have a rail with a leading edge located 27” maximum above the floor, or some other form of barrier.

Sheet A2.1

1. The guard is missing in Stairwell 120-6 at the upper landing. There needs to be a 42” high guard at the second-floor landing per 2018 IBC Sec. 1015.

Sheet A7.0

1. Detail 6 is titled as a “handrail”; however the rail is too tall for a handrail. This detail is likely a “guard” and as such its overall height need to be 42” per 2018 IBC Sec. 1015.3; however this dimension is not indicated on the detail. {Detail 7 has a similar issue; what is the height of the guard above the leading edge of the tread?}

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

Sheet M2.0

1. The COMcheck is missing from this sheet. There is a “box” labeled COMcheck on the sheet, however the box is empty.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.



Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Joel Svoboda, RA
Senior Associate
520-545-7415
joel.svoboda@stantec.com
03/10/2025 Fire New Construction Standard REVIEW COMPLETED Fire extinguishers shall be installed accordingly with the 2018 IFC Section 906
03/06/2025 PDSD Application Completeness Express REVIEW COMPLETED