Permit Number: TC-COM-0325-00419
Parcel: 136020220

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TC-COM-0325-00419
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2026 Air Balancing/Commissioning Report (Deferred Submittal) Express APPROVED
06/10/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/10/2026 Water Sterilization Report (Deferred Submittal) Express REQUIRES RESUBMIT The required water disinfection report is incomplete. Your report should include the results of a bacteriological examination by a licensed testing laboratory of the water in the distribution system after the chlorine has been purged from the system. Section 610.1 of the 2018 International Plumbing Code describes the testing requirements.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
06/10/2026 PDSD Application Completeness Express REVIEW COMPLETED
06/10/2026 Truss Design (Deferred Submittal) Express REVIEW COMPLETED