| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/05/2024 | Commercial Building | APPROVED | |||
| 06/05/2024 | Commercial Electrical | APPROVED | |||
| 06/05/2024 | Water - PDSD | APPROVED | |||
| 06/05/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/05/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Clarify how makeup air will be provided during cold weather and the evaporative cooler is not operating. Will heat be supplied to the space to prevent freezing (see Section 305.4, IPC 2018)? [Initial comment: Clothes dryer installations exhausting more than 200 CFM shall provide make up air. Show how make up air is provided. (Note that the installation of the exhaust fan will result in less make up air available to the dryers.) Reference: Section 504.6, IMC 2018.] | ||
| 06/05/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Comment not addressed. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2018.] | ||
| 05/21/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |