Permit Number: TC-COM-0324-00510
Parcel: 13811089A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0324-00510
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/05/2024 Commercial Building APPROVED
06/05/2024 Commercial Electrical APPROVED
06/05/2024 Water - PDSD APPROVED
06/05/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/05/2024 Commercial Mechanical REQUIRES RESUBMIT Clarify how makeup air will be provided during cold weather and the evaporative cooler is not operating. Will heat be supplied to the space to prevent freezing (see Section 305.4, IPC 2018)? [Initial comment: Clothes dryer installations exhausting more than 200 CFM shall provide make up air. Show how make up air is provided. (Note that the installation of the exhaust fan will result in less make up air available to the dryers.) Reference: Section 504.6, IMC 2018.]
06/05/2024 Commercial Plumbing REQUIRES RESUBMIT Comment not addressed. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2018.]
05/21/2024 PDSD Application Completeness Express REVIEW COMPLETED