Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0324-00462
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/09/2024 | Site Engineering | APPROVED | |||
| 08/21/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/15/2024 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Structural(S) Reviewer Nicholas Baptiste njnobaptiste@safebuilt.com Denied Reason: Date Completed : 7/14/2024 1:39:12 PM 1. General / Information Required. Provide components and cladding design wind pressures for roof, wall, and parapet surfaces. (REMAINS UNRESOLVED) ◦ Provide components and cladding diagram per ASCE 7-16 Figure 30.3 applicable to structure to accompany wind pressures provided including dimension ("a" or "h") for zone widths. This has not been provided on the Structural Drawings. ◦ Per ASCE 7-16 30.2.2 "The design pressure for C&C of buildings shall not be lass than a net pressure of 16 psf". Revise pressures lower than minimum value. This has not been updated on the structural drawings. |
||
| 08/21/2024 | Site Zoning | REQUIRES RESUBMIT | While the building plans appear to match the approved DP, zoning cannot approve until September 7th. Nicholas.Martell@tucsonaz.gov |
||
| 07/10/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |