Permit Number: TC-COM-0324-00462
Parcel: 13335002U

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0324-00462
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2024 Site Engineering APPROVED
08/21/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/15/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Nicholas Baptiste
njnobaptiste@safebuilt.com
Denied
Reason:
Date Completed : 7/14/2024 1:39:12 PM
1. General / Information Required. Provide components and cladding design wind pressures for roof, wall, and parapet
surfaces. (REMAINS UNRESOLVED)
◦ Provide components and cladding diagram per ASCE 7-16 Figure 30.3 applicable to structure to accompany
wind pressures provided including dimension ("a" or "h") for zone widths. This has not been provided on the Structural Drawings.
◦ Per ASCE 7-16 30.2.2 "The design pressure for C&C of buildings shall not be lass than a net pressure of 16 psf". Revise pressures lower than minimum value. This has not been updated on the structural drawings.
08/21/2024 Site Zoning REQUIRES RESUBMIT While the building plans appear to match the approved DP, zoning cannot approve until September 7th.

Nicholas.Martell@tucsonaz.gov
07/10/2024 PDSD Application Completeness Express REVIEW COMPLETED