Permit Number: TC-COM-0324-00430
Parcel: 14041124E

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TC-COM-0324-00430
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/19/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/19/2024 Air Balancing/Commissioning Report (Deferred Submittal) Express REQUIRES RESUBMIT The air balance report shows that FC-9, which is to serve the elevator shaft, was not operational at the time of testing. In addition, Room 105, which is served by FC-2, was not completed at the time of testing. Complete the air balance report once FC-9 is operational and Room 105 has been completed.
12/19/2024 PDSD Application Completeness Express REVIEW COMPLETED