Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-0324-00430
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/19/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/19/2024 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | The air balance report shows that FC-9, which is to serve the elevator shaft, was not operational at the time of testing. In addition, Room 105, which is served by FC-2, was not completed at the time of testing. Complete the air balance report once FC-9 is operational and Room 105 has been completed. | ||
| 12/19/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |