Permit Number: TC-COM-0324-00430
Parcel: 14041124E

Review Status: Approved

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TC-COM-0324-00430
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
10/02/2024 Bldg Permits - Post Review Express REVIEW COMPLETED
10/02/2024 Other Inspection Reports (Deferred Submittal) Express REVIEW COMPLETED A portion of the building is exempt from the building thermal envelope requirements set forth in
C402.1 per the following:
1. C402.1.1 Low-energy buildings exceptions #3 and #4 (City of Tucson Amendment to 2018
IECC). This S-1 Occupancy Group portion of the building has a peak design rate of energy of
0.094 W/sqft < 1.0 W/sqft.
2. The “B” Occupancy Group is separated from the Warehouse “S-1” Occupancy Group with a 6”
metal framed wall insulated with R-19 batt insulation. Above roof deck insulation value is
R-38. Both conditions exceed the minimum insulation R-value requirements.
10/02/2024 PDSD Application Completeness Express REVIEW COMPLETED
10/02/2024 Special Inspection Certificate Review (Deferred Submittal) Express REVIEW COMPLETED