Permit Number: TC-COM-0324-00396
Parcel: 121136340

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.2

Permit Number - TC-COM-0324-00396
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/19/2024 Water Sterilization Report (Deferred Submittal) Express APPROVED
12/19/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/19/2024 Air Balancing/Commissioning Report (Deferred Submittal) Express REQUIRES RESUBMIT Comment not addressed. Correct the deficiency and resubmit the report. [Initial comment: The air balance report shows that EF-1 in room 104 (Shower) is not functioning. Repair or replace the exhaust fan in order to achieve the minimum exhaust flow rate required by Table 403.3.1.1, IMC 2018. Correct the deficiency and resubmit the report. Reference: Sections 403.3.1.2 and 403.3.1.5, IMC 2018.]
12/18/2024 PDSD Application Completeness Express REVIEW COMPLETED