Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.2
Permit Number - TC-COM-0324-00396
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/19/2024 | Water Sterilization Report (Deferred Submittal) Express | APPROVED | |||
| 12/19/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/19/2024 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | Comment not addressed. Correct the deficiency and resubmit the report. [Initial comment: The air balance report shows that EF-1 in room 104 (Shower) is not functioning. Repair or replace the exhaust fan in order to achieve the minimum exhaust flow rate required by Table 403.3.1.1, IMC 2018. Correct the deficiency and resubmit the report. Reference: Sections 403.3.1.2 and 403.3.1.5, IMC 2018.] | ||
| 12/18/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |