Permit Number: TC-COM-0323-00868
Parcel: 14037068J

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0323-00868
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/16/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
08/08/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 8/7/2023 9:24:29 AM
1. The Geotechnical Report for the proposed building per International Building Code 2018, Section 1803.1 was requested, not provided. The Inspector to verify info used on the project from Geotechnical Report.

2. NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.



Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 7/30/2023 12:50:08 AM
1. Previous Comment: Clarify why the architects stamp indicates the documents were signed by Sandy Epstein when the stamp indicates the registered Architect is Isaac Sanford Epstein. Is Sandy a common name or nick name for this registered professional? Please sign the drawings with the legal name of the professional as it appears on their license. The response letter indicates that the drawings were "signed again as the name appears on the stamp" however the drawings that were summited still bear the name Sandy. Update the drawings.



Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 7/26/2023 7:15:05 PM
All corrections complied
Approved/subject to field approval



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 7/25/2023 3:22:18 PM



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 7/30/2023 9:41:59 AM
Second Plumbing Review:
1). SAME-Add gutter & down spout sizes with calculations to plan page -A1.3 -IPC 1106.3., 1106.6

2). SAME-Provide Civil site utility piping plan for continuation of of sewer & water as shown on plan pages P2.1 & P1.1 -IPC 106.3.1
3). SAME-Oil interceptor on plan page P1.1 needs to be vented - IPC 1003.9
4). OK
5). OK
6). OK
7). OK
8). OK
07/28/2023 Site Engineering REQUIRES RESUBMIT See zoning comment
07/26/2023 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0323-00868
5570 E Travel Plaza Wy. Proposed Rezoning to C-3
Trade Service and Repair - Major

TRANSMITTAL DATE: ‎April 20, 2023

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. COMMENT: Zoning has reviewed the building plans for compliance with Development Package (DP) TD-DEV-0523-00245 and although the plans appear to be in compliance until the DP is approved by all review agencies Zoning cannot approve the building plans.

If you have any questions about this transmittal, please contact Nicholas Martell at Nicholas.Martell@tucsonaz.gov.
08/16/2023 Fire New Construction REVIEW COMPLETED
07/24/2023 PDSD Application Completeness REVIEW COMPLETED The applicant will submit a withdrawal for the T21CM09821 permit.