Review Date Reviewer's Name Type of Review Description Status Comments
05/31/2023 External Reviewers - SAFEBuilt APPROVED Activity Number: TC-COM-0323-00864

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 5/30/2023 5:22:57 PM
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 4/10/2023 11:21:36 PM


Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 3/31/2023 10:37:16 PM
Approved/subject to field approval


Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Conditinally Approved
Reason:
Date Completed : 4/10/2023 6:25:29 PM
Electrical Review
By: Ron Ross PE
ED001 ELECTRICAL DEMOLITION PLAN - SOUTHEAST CORNER:
Keynote 3 or symbol for floor box is wrong per symbol legend on E000.
Could not locate Keynote 11, but one Keynote #12 is possibly misnumbered.
ED002 ELECTRICAL DEMOLITION PLAN - SOUTHWEST CORNER: Keynote 3 or symbol for floor box is wrong per symbol legend on E000.
ED004 DEMO LIGHTING PLAN - SOUTHWEST CORNER: Could not locate Keynote #5.
E101 POWER PLAN - SOUTHEAST CORNER: Could not locate Keynote #7.
E102 POWER PLAN - SOUTHWEST CORNER: Could not locate Keynote #13.
E600 PANEL SCHEDULES: 400-amp Panels DPA and DPB are not in agreement with 200-amp panels shown on E400. Coordinate, either design is code compliant.


Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 4/8/2023 12:34:50 PM
First Plumbing Review: OK Subject To Field Inspections & Manufacture Specs
05/26/2023 Site Zoning APPROVED
05/31/2023 Bldg Permits - Post Review Express REVIEW COMPLETED
05/25/2023 PDSD Application Completeness Express REVIEW COMPLETED