Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2023 Site Zoning APPROVED
04/19/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
04/06/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number:TC-COM-0323-00836


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
DENIED
1. Refer to Mechanical Drawing m1.1, Mechanical Roof Plan – New Work. The Plan shows New Condenser Units HPCU 1 thru HPCU 9 and CU 1. The Mechanical Drawing m3.1, Mechanical Schedules show the units weights up to 400 pounds. Verify the adequacy of the roof structure to support these loadings by providing Structural Calculations for the Roof Structural Members to support these additional loads.
2. All Calculations shall be sealed and signed by Professional Engineer registered with State of Arizona per Section 107.1 of International Building Code 2018. Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings

BUILDING REVIEW COMMENTS:
DENIED
1. Sheet G2.0: There is a distinct difference between occupancy classification and occupancy use. The exceptions provided in Section 303.1.2 apply to that of classification and the requirements of max. allowable area, height, stories, mix-use requirements and overall classification of the building. The waiting room is considered as business in the overall context of the structure and can comply with the business requirements previously mentioned. However, when calculating occupant loads, one must calculate based on the use of the space. The waiting room's use is assembly and the occupant load must be calculated as such in accordance with Section 1004 and Table 1004.5. Provide corrected occupant load calculations, Additionally, provide the occupant load factor used for each space. Updated all associated occupant load based requirements. (number of exits, egress widths, plumbing fixture calculations, etc.)
2. Sheet G2.0: There are number of doors that may be swing in the incorrect direction based on updated occupant load calculations. Correct as necessary.


MECHANICAL REVIEW COMMENTS:
CONDITIONALLY APPROVED
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
DENIED
el101 new lighting plan: Need to provide an interior lighting Comcheck to show IECC compliance.
ep101 new power plan:
Electrical Equipment Keyed Note #6 has a 75 KVA transformer mounted above a walkway. This exceeds 50 KVA, which may be applicable and the largest allowed per NEC 450.13(B) for this type of application.
Detail 2 has existing fire alarm panel behind existing transformer and violates NEC 110.26 working clearances for panels. The Fire alarm panel should be relocated to correct this code deficiency.
ep701 single line diagram, fire alarm diagram, nurse call riser diagram: Keynote #3 next to meter/transformer should be #2.


PLUMBING REVIEW COMMENTS:
CONDITIONALLY APPROVED
First Plumbing Review= Ok Subject To Field Inspections


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
04/14/2023 Site Engineering REQUIRES RESUBMIT Project: TC-COM-0323-00836 and TC-DMO-0423-00089

Address: 6365 E TANQUE VERDE RD Unit:UNIT 100
NOTE: ONLY ONE (1) FUP IS NEEDED FOR THE BUILDING PERMIT AND DEMO PERMIT

This project is within a regulated floodplain and requires a Floodplain Use Permit (FUP.)

Please start a new FUP at our permit application web page:

https://tdc-online.tucsonaz.gov/#/home

NOTE: Documentation of a cost estimate from your contractor will be required if this project involves any reconstruction, repair, rehabilitation, structurally connected addition, or other improvement of an existing structure (including TI’s and solar). Construction of separate builds/new structures does not require a cost estimate to be provided.

Instructions:

1. Navigate into the current project in the “My Work” tab. Within the permit, navigate to the “Sub-Records” tab and click “Apply” on the Floodplain Use Permit Sub-Record

2. Locations -> Confirm the location is accurate to the project. Click “Next”

3. Type -> Fill in the “Square Feet” and “Valuation” boxes with the project area and a contractor-provided cost estimate (See note above: for new structures, input 0). Click “Next”

4. Contacts -> Confirm contacts and add any additional contacts if applicable. Click “Next”

5. More Info -> This will be filled in by the engineer assigned to your case, Click “Next”

6. Attachments -> Please attach the project plan, supporting documentation for the cost estimate (if applicable), and a drainage/hydrology report (if applicable). Click “Next”

7. Signature -> Read the statement and type your name. Sign your name below (You may Enable Type Signature to have the software sign for you.) Click “Next”

8. Review and Submit -> Review all information to ensure accuracy. Click “Submit”

Contact Scott Haseman at scott.haseman@tucsonaz.gov, Stephen Blood at Stephen.Blood@tucsonaz.gov, or Loren Makus at Loren.Makus@tucsonaz.gov if you have any questions about the FUP.
03/27/2023 Fire New Construction REVIEW COMPLETED
03/22/2023 PDSD Application Completeness REVIEW COMPLETED