Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0323-00792
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/16/2023 | Commercial Electrical | APPROVED | |||
| 03/17/2023 | Site Zoning | APPROVED | |||
| 03/23/2023 | Site Engineering | NOT REQUIRED | |||
| 04/07/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/27/2023 | Commercial Mechanical | REQUIRES RESUBMIT | 1. As an R-4 occupancy with 6 or more occupants, this dwelling unit is beyond the scope of the International Residential Code. The relevant code for the mechanical aspects of this project is the 2018 International Mechanical Code with Local Amendments. Change the code references from the IRC to the IBC, IMC, IECC, or other appropriate code. 2. Provide mechanical ventilation for the building. Reference: Section R403.6, IECC 2018. 3. Secure the refrigerant circuit access ports of the condensing unit to prevent unauthorized access. Reference: Section 1101.10, IMC 2018. |
||
| 03/27/2023 | Commercial Plumbing | REQUIRES RESUBMIT | Reduced pressure backflow prevention assemblies are required at the water meter for licensed, personal care facilities. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf. | ||
| 04/07/2023 | Commercial Structural | REQUIRES RESUBMIT | Provide written responses to all review comments: 1) General: This is a a change of use from a single family residence to a commercial assisted living facility (R-4). Per IBC Section 420.4, this building will require an automatic sprinkler system. 2) Sheet 2: Code analysis shall be updated to reflect occupancy classification of R-4 and the requirement for a automatic sprinkler system. 3) Provide a complete egress plan with the next submittal. |
||
| 03/21/2023 | Fire New Construction | REQUIRES RESUBMIT | Plans state that the use is an adult care facility with 6 occupants. The occupancy classification then would be an R-4. All R-4's require fire sprinklers. Please let us know if you are Condition 1 and or Condition 2 so that we can advise what type of fire sprinklers you will need to install. A note shall be on the drawings showing that fire sprinklers are being installed and the occupancy type shall be corrected with R-4 and the Condition. Questions: Jennifer Peel-Davis Tucson Fire Department Fire Plans Examiner Fire Inspector I, II and Fire Alarm Plans Examiner Jennifer.Peel-Davis@Tucsonaz.gov Desk: 520-837-7033 |
||
| 03/16/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |