Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0226-00265
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/17/2026 | Commercial Building Standard | APPROVED | |||
| 03/16/2026 | Site Zoning Standard | APPROVED | |||
| 03/11/2026 | Outdoor Lighting Standard | NOT REQUIRED | No modifications to the outdoor lighting. | ||
| 02/26/2026 | Site Engineering Standard | NOT REQUIRED | |||
| 03/18/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/12/2026 | Commercial Electrical Standard | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0226-00265 (1840 E VALENCIA RD Unit:BLDG 8 TUCSON, AZ 85706) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC). Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov 1. Show PV interconnection in compliance with NEC 705.32. Reference also NEC 230.95. 705.32 Ground-Fault Protection. Provide a GFCI PV backfeed breaker at the main panel/switchboard. |
||
| 03/18/2026 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 02/24/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |