Permit Number: TC-COM-0226-00244
Parcel: 123100280

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0226-00244
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2026 Commercial Building Standard APPROVED
03/12/2026 Commercial Electrical Standard APPROVED
03/16/2026 Commercial Mechanical Standard APPROVED
03/16/2026 Site Zoning Standard APPROVED
03/16/2026 Water - PDSD Standard APPROVED
03/11/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
02/26/2026 Site Engineering Standard NOT REQUIRED
03/18/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/16/2026 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Show that the proposed reduced pressure zone backflow prevention assembly will be installed in an accessible, non-concealed location per the manufacturer’s installation instructions. The air gap and drain line from the reduced pressure zone backflow prevention assembly shall be piped from the relief valve connection to a clearly visible discharge location with an air gap and that will prevent the occurrence of water damage. Reference: Sections 608.14 and 608.14.2, IPC 2024.
2. The proposed drain box has a 2” waste outlet; reducing the trap to 1-1/2” is not allowed. Reference: Section 704.2, IPC 2024.
3. Provide a detail; showing how the new lavatory, L-1, and drain box, DB-1, are to be connected to the existing waste and vent piping. Reference: Sections 1002.1, IPC 2024.

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
03/18/2026 Fire New Construction Standard REVIEW COMPLETED
02/24/2026 PDSD Application Completeness Express REVIEW COMPLETED