Permit Number: TC-COM-0226-00239
Parcel: 12217264D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0226-00239
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2026 Commercial Building Standard APPROVED
04/14/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/14/2026 Commercial Plumbing Standard REQUIRES RESUBMIT The mixing valve specified in keynote 17 on sheet A2.0 is a manual mixing valve. Provide a thermostatic mixing valve conforming to ASSE 1070. [Initial comment: Provide tempered water for the lavatories and public hand-washing sinks in restrooms with a device conforming to ASSE 1070. Reference: Section 419.5, IPC 2024.]
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
03/26/2026 PDSD Application Completeness Express REVIEW COMPLETED