Permit Number: TC-COM-0226-00220
Parcel: 108200400

Address:
1101 E ROGER RD

Review Status: In Review

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0226-00220
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
02/26/2026 Site Engineering Standard NOT REQUIRED
N/A Bldg Permits - Post Review Express PENDING ASSIGNMENT
N/A Commercial Building Standard PENDING ASSIGNMENT
N/A Fire New Construction Standard PENDING ASSIGNMENT
03/05/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0226-00220 (1101 E ROGER RD TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
Plans shall include (as necessary for scope of work), but may not be limited to items below:
2. Provide an electrical plan showing the location of all electrical equipment, outlets, lighting fixtures, etc.
3. Provide the equipment size and rating and a line diagram for the existing and new service. Include the bus size and AIC rating, NEC 408.3, IBC 107.1.
4. Show all wiring methods in detail for all new electrical conductors and branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4.
5. Provide a panel schedule, showing all circuits that are added. NEC arts;300 and 408.4. Include panel bus rating and A.I.C. rating. IBC 107.1.
6. Designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each existing, new or modified light fixtures, receptacles, gate operator, equipment disconnect switch, etc., NEC arts;300 and 408.4. IBC 107.1. Each electrical outlet should be labeled by panel and circuit number.
7. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, [NEC 210.52(C)(1)] and [NEC 210.52(B)(1)]. GFCI protected, [NEC 210.8(A)]. The provided plans only show one kitchen countertop circuit.
8. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, [NEC 210.11(C)(3)] and [NEC 210.52(D)]. GFCI Protected, [NEC 210.8(A)]. The receptacle in the bathroom cannot share the circuit with any other locations.
9. Show compliance with receptacle replacement and distances per NEC 210.52, for both wall space and kitchen counter tops. >>> Each unit is missing required receptacles along the walls or counter tops per this section.

Additional comments may be forthcoming with complete electrical plans for the proposed site and electrical work.
03/10/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0226-00220
ADDRESS/PARCEL: 1101 E ROGER RD TUCSON, AZ 85719

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:
1. Provide a complete set of mechanical plans. Plans must be sealed by an Arizona-registered design professional. Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Show all proposed mini-split units on the plans. The addition of AC units will require a heating/cooling load calculation to justify the capacities of the units being installed (Sections R403.7, IECC 2018). The units themselves will also have to comply with Sections R403.1 and R503.1.2, IECC 2018 for efficiency, controls, and ductwork.
03/10/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0226-00220
ADDRESS/PARCEL: 1101 E ROGER RD TUCSON, AZ 85719

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:
1. Provide a complete set of plumbing plans. Plans must be sealed by an Arizona-registered design professional. Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Demonstrate that each bathroom and kitchen will be provided with mechanical ventilation. Reference: Table 403.3.2.3, IMC 2024.
3. On the site plan, show each building sewer and how each building sewer connects to the public sewer. Reference: Section 107.2.1, IBC 2024.
4. Show the location of all cleanouts for the building sewer. Reference: Section 703.5, IPC 2024.
5. Provide a plumbing fixture schedule and specify that all proposed plumbing fixtures shall be listed by a third-party certification agency as complying with the relevant standards. Reference: Section 303.4, IPC 2024.
6. Show the location of the water heater on the floor plans. Provide specifications and listing information for the water heaters, and indicate the fuel source. Reference: Sections 303.2 and 501.5, IPC 2018 and Section 107.2.1, IBC 2024.
7. Please provide roof drainage and scupper size calculations based on the 100-year hourly rainfall rate for Tucson, 3” per hour. Reference: Sections 1101.7, 1106, and 1108, IPC 2018.
a. Demonstrate the direction of roof drainage on the plans.
b. Also, the roof plan indicates that the roof drainage from proposed Unit 1 is flowing away from the scuppers. Please clarify.
8. Provide overflow protection for the roof. Reference: Sections 1108, IPC 2024.
03/10/2026 Water - PDSD Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0226-00220
ADDRESS/PARCEL: 1101 E ROGER RD TUCSON, AZ 85719

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:
1. Show the size and location of the water meter on the site plan, and indicate the route, size, and material of the water service piping serving each unit. Reference: Section 107.2.1, IBC 2024.
02/19/2026 PDSD Application Completeness Express REVIEW COMPLETED
03/11/2026 Site Zoning Standard VOID PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-0226-00220
1101 E. Roger Rd. Tucson, AZ 85719
Triplex to Fourplex (1st Review)

TRANSMITTAL DATE: 3/11/2026

This site is located in the R-2 zone (UDC 4.7.9).

1. Comment: As of January 1, 2026, parcels are now allowed to have 4 units on them and not be considered a commercial development. I consulted with management and was told to have you please apply for a Residential New Dwelling permit for your fourplex. I will VOID my review to prevent further movement with this permit.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.