Permit Number: TC-COM-0226-00202
Parcel: 115180050

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0226-00202
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/09/2026 Water - PDSD Standard APPROVED
03/04/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
03/10/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/10/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Provide means of egress drawings and analysis demonstrating compliance with the occupant load, width, and travel distance requirements for the proposed R-2 occupancy. Please demonstrate the egress capacity meets or exceeds the occupant load as specified in the IBC for the new occupancy. IEBC 1011.5.3
A. Required information:
B. Occupant load per floor
C. Exit capacity calculations
D. Stairway width
E. Door width
2. IEBC 106.2.3 To include the exit discharge path to the public way IBC 1028
3. Please amend the construction documents to include a dimensioned floor plan with labels for each space in the room for each building and floor. IEBC 106.2.1
4. Please provide a statement indicating these to be sleeping units or dwelling units IEBC 106.2.1
5. The last C of O’s issued for these buildings have an occupancy group as I-3 Shelter Care Facility. Please amend the project narrative to indicate the occupancy change is from an I-3 to an R2. IBC 107.2.1
6. Please provide a code analysis for each building to include the following.
A. Construction Type
B. Occupancy Type
C. Fire Sprinklers - Yes or No If yes indicate the sprinkler type
D. Fire Alarm - Yes or No
E. Design Occupant Load
F. Total Square footage of The Occupied Space
7. Please amend the new Occupancy Group designation and remove the (assumed) after the R-2
8. Please amend the plans to include the required separation walls and horizontal separation as required by IBC 420.2 (Section 708) and IBC 420.3 (Section 711) respectively
9. Please amend the plans to demonstrate the 1-hour corridor rating as hotels sometimes have non-rated corridors IBC 1020
10. Please amend the plans to demonstrate the stairway handrails are in compliance with IEBC 1011.5.4
11. Please amend the plans to demonstrate existing guards are in compliance with IEBC 804.12 IEBC 1011.5.5
12. IEBC 306.7 requires that accessibility be provided to the altered spaces. Where the existing path of travel elements, which entails a primary entrance, a primary path of travel, sanitary facilities serving the area, a drinking fountain, and signs. If these items are in full compliance with the current code, provide a statement indicating this on the cover sheet of the drawings. Otherwise, accessibility upgrades shall be required in accordance with IEBC.306.7. 1. If the cost of providing or upgrading the items above to be accessible is disproportionate to the cost of construction (exceeds 20% of the cost of construction not including accessibility upgrades), please provide information to verify construction costs.
Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
03/04/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review
TC-COM-0226-00210 (1601 N ORACLE RD Unit:BLDG 1 TUCSON, AZ 85705)
TC-COM-0226-00211 (1601 N ORACLE RD Unit:BLDG 2 TUCSON, AZ 85705)
TC-COM-0226-00212 (1601 N ORACLE RD Unit:BLDG 3 TUCSON, AZ 85705)
TC-COM-0226-00202 (1601 N ORACLE RD Unit:BLDG 4 TUCSON, AZ 85705)
TC-COM-0226-00213 (1601 N ORACLE RD Unit:BLDG 7 TUCSON, AZ 85705)
TC-COM-0226-00214 (1601 N ORACLE RD Unit:BLDG 8 TUCSON, AZ 85705)

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide as-built electrical plans showing all receptacles and outlets.
2024 IEBC
1007.4 Number of electrical outlets.
Where the occupancy of an existing building or part of an existing building is changed, the number of electrical outlets shall comply with NFPA 70 for the new occupancy.
The number of outlets that are inherent to an area undergoing a change of occupancy must meet NFPA 70 requirements for the new occupancy.

2. Provide a panel schedule, showing all existing circuits that and any that are added, removed or modified. NEC arts;300 and 408.4. Include panel bus rating and A.I.C. rating. IBC 107.1.
3. Designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each existing, receptacles, etc., NEC arts;300 and 408.4. IBC 107.1. Each electrical outlet should be labeled by panel and circuit number.
03/09/2026 Commercial Mechanical Standard REQUIRES RESUBMIT Clarify how many units are classified as dwelling units (i.e., with full eating and eating facilities) versus how many are just sleeping units. If a large number of sleeping units are present, are there also cafeterias or dining rooms (Group A-2) areas present? Reference: Section 107.2.1, IBC 2024.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
03/09/2026 Commercial Plumbing Standard REQUIRES RESUBMIT Clarify how many units are classified as dwelling units (i.e., with full eating and eating facilities) versus how many are just sleeping units. If a large number of sleeping units are present, are there also cafeterias or dining rooms (Group A-2) areas present? Reference: Section 107.2.1, IBC 2024.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
03/09/2026 Fire New Construction Standard REQUIRES RESUBMIT -Change of use shall comply with Chapter 10 of the IEBC. This would require meeting the fire protection requirements of the current IFC. Specifically 907.2.9 for R2 fire alarms. The existing fire alarm will most probably not be code compliant for an R2 occupancy if a fire alarm is required. A fire alarm that complies with this section (R2 907.2.9) will be required unless you meet the exceptions. It appears you might meet exception #3 for these three buildings. Please explain.
john.vincent@tucsonaz.gov
5203495581
03/10/2026 Site Engineering Standard REQUIRES RESUBMIT Site Engineering Review

TC-COM-0226-00202
1601 N ORACLE RD BLDG 4

Description: Occupancy change from R-1 to R-2. Project does not propose any alterations.

Site Engineering comments are as follows:

1. As requested by Zoning, please provide detailed parking calculations to establish whether parking is sufficient for the new occupancy.
2. Flood plain use permits may be required depending on the parking requirements. If a Development Package is required, FPU permits will be, as well.

To re-submit, visit the Tucson Development Center Online at:
https://tdc-online.tucsonaz.gov/#/home

The instructions for resubmittal can be found at: Revisions and Resubmittals

Engineering Associate: Ryan Insalaco
ryan.insalaco@tucsonaz.gov
03/09/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-0226-00202
1601 N. Oracle Rd. Bldg. 4 Tucson, AZ 85705
Occupancy change from R-1 to R-2 (1st Review)

TRANSMITTAL DATE: 3/9/2026

This site is zoned I-1 (UDC 4.7.29).

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: As this project proposes a change of use from Traveler’s Accommodation to Multifamily, please include detailed parking calculations which clearly show the new use is meeting the minimum parking requirements per UDC Table 7.4.4-1. If the minimum parking requirements cannot be met, a development package submittal may be required.
2. Comment: Please include the following note on the first page of your submittal: Multifamily Development is a permitted use in the I-1 zone as an "Adaptative Reuse" allowed per State of Arizona House Bill 2297 of 2024.
3. Comment: As this site is made up of multiple parcels (115180050 and 115180200), either a Lot Combination or a recorded Covenant Regarding Development and Use of Real Property will be required. Please contact Pima County if you wish to proceed with a Lot Combination request. The Covenant can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/submission-documents/covenant-regarding-development-and-use-of-real-property-udc-with-release.pdf.
4. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
02/18/2026 Addressing Validation REVIEW COMPLETED Address updated and issue satisfied - 2/17

If you have questions regarding this review, please contact Drew Szentesy at Drew.Szentesy@tucsonaz.gov or the team at PDSD-Permits@tucsonaz.gov
If building other buildings are being included on this permit, please submit an address change request through permit sub records and ensure all numbers are included on the construction plans.
For help navigating sub records: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/withdraws-and-extensions.pdf
02/13/2026 PDSD Application Completeness Express REVIEW COMPLETED