Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-0226-00159
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/16/2026 | Water Sterilization Report (Deferred Submittal) Express | APPROVED | |||
| 04/16/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/16/2026 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0226-00159 ADDRESS/PARCEL: 1530 W GRANT RD TUCSON, AZ 85745 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov COMMENTS: 1. The submitted air balance report indicates that the Make-Up Air Unit (MAU) and existing Exhaust Fan (EF-1) are operating below the design values shown on the approved construction documents. Please provide written approval from the Engineer of Record acknowledging and accepting these deviations, or revise the mechanical design and associated documents to reflect actual operating conditions. |
||
| 04/16/2026 | County Health Inspection (Deferred Submittal) Express | REVIEW COMPLETED | |||
| 04/15/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |