Permit Number: TC-COM-0226-00146
Parcel: 105102690

Address:
4214 N 1ST AV

Review Status: In Review

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0226-00146
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
N/A Bldg Permits - Post Review Express PENDING ASSIGNMENT
N/A Commercial Building Standard PENDING ASSIGNMENT
N/A Commercial Mechanical Standard PENDING ASSIGNMENT
N/A Commercial Plumbing Standard PENDING ASSIGNMENT
N/A Site Zoning Standard PENDING ASSIGNMENT
N/A Water - PDSD Standard PENDING ASSIGNMENT
11/02/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0226-00146 (4214 N 1ST AV TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. The provided lumen calculations for total allowable lumens is incorrect. Table 401.1 provides the maximum lumens per acre. Per Sheet A0.00, Project Information, Property Information, the total lot size is 0.5536 acres. The total allowable lumens for this site is the Lumens per acre from Table 401.1, multiplied by the developed area or lot size.
2. Maximum lumens allowed = 175,000 lumens/acre * 0.5536 acres = 96,880 lumens.
3. Maximum unshielded lumens allowed = 11,000 lumens/acre * 0.5536 = 6,089.6 lumens.
4. The total unshielded lumens proposed exceeds the Maximum unshielded lumens allowed.
5. Provide an updated lighting plan to show a maximum unshielded lumens under the allowable limit.
10/30/2026 Site Engineering Standard REQUIRES RESUBMIT Permit Activity Number: TC-COM-0226-00146 (3rd Review)
Project: Scooter’s Coffee
Location: 4214 N 1ST AV
Review Date: 10/30/2026
Reviewer: John Mounsey – Engineering Associate - Site Engineering
Reviewer Contact: John.Mounsey@tucsonaz.gov

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed to ensure final approval from Site Engineering.
To help speed up your resubmittal and facilitate shorter review timelines, please include a response letter along with your updated plans and any supporting calculations. In your response letter, address each comment individually and explain what changes were made and where they can be found in the plans. Submit your response letter and updated plan set as two separate files.

Site Engineering Review Comments:
Building plans, including the site design, must match what was approved in Development Package (Site Plan) TD-DEV-0726-00178. Sheet A0.00 in the Building plans, does not match the approved site design from the development package. Revise the plans to carry the same layout shown in the approved plans.

If you have any questions or concerns, please contact John Mounsey at John.Mounsey@tucsonaz.gov
10/26/2026 PDSD Application Completeness Express REVIEW COMPLETED