Permit Number: TC-COM-0225-00379
Parcel: 12809015A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0225-00379
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2025 Commercial Electrical Standard APPROVED
05/13/2025 Commercial Plumbing Standard APPROVED
05/13/2025 Water - PDSD Standard NOT REQUIRED
05/13/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/13/2025 Commercial Mechanical Standard REQUIRES RESUBMIT The minimum continuous exhaust flowrate for the men’s restroom is 200 CFM (3 urinals plus 1 water closet) and 150 CFM of continuous exhaust for the women’s restroom (3 water closets). [Initial Comment: Provide a minimum exhaust flow rate of 50 CFM per water closet or urinal if the exhaust is continuous, 70 CFM if the exhaust is intermittent. Reference: Section 403.3.1.1 and Table 403.3.1.1, IMC 2018.]
04/23/2025 PDSD Application Completeness Express REVIEW COMPLETED