Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0225-00379
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/29/2025 | Commercial Electrical Standard | APPROVED | |||
| 05/13/2025 | Commercial Plumbing Standard | APPROVED | |||
| 05/13/2025 | Water - PDSD Standard | NOT REQUIRED | |||
| 05/13/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/13/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | The minimum continuous exhaust flowrate for the men’s restroom is 200 CFM (3 urinals plus 1 water closet) and 150 CFM of continuous exhaust for the women’s restroom (3 water closets). [Initial Comment: Provide a minimum exhaust flow rate of 50 CFM per water closet or urinal if the exhaust is continuous, 70 CFM if the exhaust is intermittent. Reference: Section 403.3.1.1 and Table 403.3.1.1, IMC 2018.] | ||
| 04/23/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |