Review Date Reviewer's Name Type of Review Description Status Comments
03/12/2025 Commercial Building NOT REQUIRED
03/18/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/18/2025 Site Engineering REQUIRES RESUBMIT TC-COM-0225-00349 (=
1601 W VALENCIA RD

1. Please show dimensions. Per TSM 7-01.4.2B - When bollards or architectural features are used to provide physical separation, the maximum separation between the barriers is five feet clear.
2. See Zoning Comments.

Chris Arrington
chris.arrington@tucsonaz.gov
03/10/2025 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0225-00349
1601 W VALENCIA RD. - C-1
Financial Service (1st Review)

TRANSMITTAL DATE: ‎March 10, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-1 zone (UDC 4.7.20). Financial Service is an approved use in the zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.4.L.1 & .3 and 4.9.13.O.

1. The proposed location of the proposed “THREE (3) BOLLARDS WITH SLEEVES (TYP.)” as shown on the plan are reducing the “C” minimum parking space depth of 18’, UDC Figure 7.4.6-A & Table 7.4.6-1. Per UDC Article 7.4.10.D.7 a Parking Design Modification Request (PDMR) may modify a dimensional requirement by no more than 10%. Provide a dimension from the proposed bollard north to the end of the parking space. If the parking space is at least 16.2’ in depth but less than 18.0’ you will need to submit a PDMR to reduce the length. If the parking space is less than 16.2’ either the bollards will need to be relocated or a Board of Adjustment for Variance will need to be submitted and approved.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.