Permit Number: TC-COM-0225-00299
Parcel: 14029003H

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0225-00299
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/21/2025 Commercial Electrical Standard APPROVED
03/21/2025 Outdoor Lighting Standard APPROVED
04/03/2025 Site Zoning Standard APPROVED
04/07/2025 Site Engineering Standard NOT REQUIRED
04/07/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/21/2025 Commercial Building Standard REQUIRES RESUBMIT 1. 1. Sheet C0.01, 2018 IBC 306.2 Moderate-hazard factory industrial, Group F-1. Factory industrial uses that are not classified as Factory Industrial F-2 Low Hazard shall be classified as F-1 Moderate Hazard. Provide narrative describing the function of the space. OUTSTANDING COMMENT: The comment is not requesting details of a product, however the effects of the operation is required in order to determine potential hazards involved and applicability of the code sections related dust hazards, hazardous materials, etc...DMA
2. Sheet C0.01, 2018 IBC Ch 5; Provide complete building Data to include adjacent space with overall building square footage. Also include historical analysis to determine if design was a separated mixed use, etc... OUTSTANDING COMMENT: Information is required for a complete review and to ensure compliance with the code (107.2). DMA
3.Sheet A1.01; Mezzanine not detailed on means of egress plan or identified on building data. Also provide a detailed floor plan and occupancy/use of the space. OUTSTANDING COMMENT: Space exists and is subject to decision of the City of Tucson as to approriate and acceptable methods to render space inaccessible and unoccupiable. DMA
03/21/2025 Commercial Mechanical Standard REQUIRES RESUBMIT
03/21/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Sheet P2.01, 2018 IPC; Provide detailed plumbing isometrics for new work with enlarged details of connections to existing sewer. OUTSTANDING COMMENT: City of Tucson to determine if plans can be accepted without isometrics. DMA
2. Sheet P2.01, 2018 IPC 1003.1 Where required. Interceptors and separators shall be provided to prevent the discharge of oil, grease, sand and other substances harmful or hazardous to the public sewer, the private sewage system or the sewage treatment plant or processes. Plan indicates floor drains located in the F-1 area. OUTSTANDING COMMENT: Registrant states no interceptor is required due to install of a curb. No referenced exception is provided. In addition the Registrant has not identified the processes, materials and potential hazards taking place. DMA
03/18/2025 PDSD Application Completeness Express REVIEW COMPLETED