Permit Number: TC-COM-0225-00299
Parcel: 14029003H

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0225-00299
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2025 Water - PDSD Standard APPROVED
03/14/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/28/2025 Commercial Building Standard REQUIRES RESUBMIT Sheet C0.01; For questions regarding Plan Review comments please contact: Dino M. Accardo, MCP, CBO, E: daccardo@willdan.com. Fire Plan Review is NOT within the scope of this review. All applicable comments will be followed with the initials, DMA.

1. Sheet C0.01, 2018 IBC 306.2 Moderate-hazard factory industrial, Group F-1. Factory industrial uses that are not classified as Factory Industrial F-2 Low Hazard shall be classified as F-1 Moderate Hazard. Provide narrative describing the function of the space. DMA
2. Sheet C0.01, 2018 IBC Ch 5; Provide complete building Data to include adjacent space with overall building square footage. Also include historical analysis to determine if design was a separated mixed use, etc... DMA
3. Sheet G1.00, 2018 IBC1009.7 Exterior areas for assisted rescue. Exterior areas for assisted rescue shall be accessed by an accessible route from the area served. Where the exit discharge does not include an accessible route from an exit located on the level of exit discharge to a public way, an exterior area of assisted rescue shall be provided on the exterior landing in accordance with Sections 1009.7.1 through 1009.7.4. DMA
4. Sheet A1.01; Mezzanine not detailed on means of egress plan or identified on building data. Also provide a detailed floor plan and occupancy/use of the space. DMA
5. Sheet A1.08, 2018 IBC 1010.1.9.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate. DMA
6. Sheet S3.0, 2018 IBC Ch 17; Submit completed Tucson Specila Insp Certificate for all required special inspections. DMA
7. Sheet S3.0, 2018 IBC 1808.1 General. Foundations shall be designed and constructed in accordance with Sections 1808.2 through 1808.9. Shallow foundations shall satisfy the requirements of Section 1809. Deep foundations shall satisfy the requirements of Section 1810. Plan details do not indicate foundation support for new mezzanine. DMA
02/28/2025 Commercial Electrical Standard REQUIRES RESUBMIT 1. Sheet E0.1, 2018 IECC; Provide a Energy Certificate for lighting. DMA
03/12/2025 Commercial Mechanical Standard REQUIRES RESUBMIT
02/28/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Sheet P2.01, 2018 IPC; Provide detailed plumbing isometrics for new work with enlarged details of connections to existing sewer. DMA
2. Sheet P2.01, 2018 IPC 1003.1 Where required. Interceptors and separators shall be provided to prevent the discharge of oil, grease, sand and other substances harmful or hazardous to the public sewer, the private sewage system or the sewage treatment plant or processes. Plan indicates floor drains located in the F-1 area. DMA
03/12/2025 Outdoor Lighting Standard REQUIRES RESUBMIT
03/14/2025 Site Engineering Standard REQUIRES RESUBMIT Address Zoning comments regarding mezzanine.
Joshua Garcia
joshua.garcia@tucsonaz.gov
03/06/2025 Site Zoning Standard REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0225-00299
3480 E BRITANNIA DR. - I-1
TI UDC Use Unknown (1st Review)

TRANSMITTAL DATE: ‎March 6, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the I-1 zone (UDC 4.7.29). UDC Use Unknown

1. Provide a use as defined in the UDC. Once provided additional comments may be forthcoming.

2. The plan show a new mezzanine. This mezzanine constitutes an expansion of gross floor area (GFA). Either provide an approved site/development package that shows the mezzanine square footage accounted for or a new development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan, UDC Article 3.3.3.G.2.c,

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
02/24/2025 Fire New Construction Standard REVIEW COMPLETED Paint Booths required to be a separate submittal.
02/13/2025 PDSD Application Completeness Express REVIEW COMPLETED