Permit Number: TC-COM-0225-00273
Parcel: 107121100

Address:
2936 N STONE AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0225-00273
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/12/2025 Site Engineering Standard APPROVED
03/03/2025 Site Zoning Standard APPROVED
03/12/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/05/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Provide structural calculations and design and construction drawings prepared by an Arizona licensed registrant an required by the City of Tucson Commercial submittal requirements. IBC 107.2.1
A. The design should indicate the existing roof structure will be able to support the weight of the rooftop PV system.
B. The design should also show the attachment can resist any uplift.

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
03/03/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0225-00273 (2936 N STONE AV TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), International Energy Conservation Code (IECC), 2017 National Electrical Code (NEC).

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
2. Provide grounding and grounding electrode systems for detached structures per NEC 250.32.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
02/19/2025 Fire New Construction Standard REVIEW COMPLETED System and installation shall comply with the 2024 IFC Chapter 21
02/11/2025 PDSD Application Completeness Express REVIEW COMPLETED