Permit Number: TC-COM-0225-00271
Parcel: 13824162A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0225-00271
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2025 Commercial Mechanical Standard APPROVED
03/03/2025 Site Zoning Standard APPROVED
03/06/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/06/2025 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0225-00271
ADDRESS/PARCEL: (1601 W VALENCIA RD TUCSON, AZ 85746)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval.

COMMENTS:
1. RESTROOMS:
a. Comply to Signage requirement per IBC 2902.4 as well as identifying accessible elements per IBC 1111.1 and IBC 1111.2 for Directional signage indicating the route to the nearest like accessible element (installed sign in the lobby area).
b. Lavatories installed in all buildings shall be provided with automatic faucets dispensing a maximum of 0.25 gallon per metering cycle. Additionally, they should run for a minimum of 10 seconds. IPC as amended 419.6, ICC A117.1 606.4 2. Amend plans to specify tempered water for lavatories in public toilet facilities with Tempered water shall be delivered from lavatories and group wash fixtures located in public toilet facilities provided for customers, patrons and visitors. Tempered water shall be delivered through an approved water-temperature limiting device that conforms to ASSE 1070/ASME A112.1070/CSA B125.70 or CSA B125.3.
2. DRINKING FOUNTAIN: Not identified on the plan
a. For the business occupancy, water coolers can be substituted for drinking fountains per IBC 2902.1 and IPC 410.1
3. OFFICE 103 and LOBBY 119:
a. Glazing adjacent to doors. Glazing in an individual fixed or operable panel adjacent to a door where the nearest vertical edge of the glazing is within a 24-inch arc of either vertical edge of the door in a closed position and where the bottom exposed edge of the glazing is less than 60 inches above the walking surface shall be considered to be a hazardous location per IBC 2406.4.2 Per IBC 2406.4 Hazardous locations require safety glazing materials.
4. TELLER ROOM 122, BREAK ROOM, RECEPTION DESK, OFFICE: Provide drawings illustrating the following.
a. Ensure that the facility is accessible complying to the ICC/ANSI A117.1 for both Employees and Customers. The tops work surfaces 902.4: shall be 28 inches min and 34 inches max above the floor. Parallel approach 904.3.2: the public use side of the counter surface 36 inches in length minimum. Forward approach 904.3.3: the public use side of the counter surface 30 inches minimum in length. Knee clearance 306.3: between 9 inches and 27 inches above the floor. Maximum depth 306.3.2: extend 25 inches maximum under an element at 9 inches above the floor. Minimum depth 06.3.3: Where clear floor space complying with Section 305, the knee clearance shall be 11 inches minimum in depth at 9 inches above the floor, and 8 inches minimum in depth at 27 inches above the floor.
b. Please resubmit.
03/03/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0225-00271 (1601 W VALENCIA RD TUCSON, AZ 85746)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), International Energy Conservation Code (IECC), 2017 National Electrical Code (NEC).

1. Provide complete compliance with the 2018 IECC for the interior.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov