Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0225-00264
Parcel: 12809006B

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TC-COM-0225-00264
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/21/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/21/2025 Concrete Installation Inspection (Deferred Submittal) Express REQUIRES RESUBMIT Submit concrete reports
10/21/2025 Masonry Inspection (Deferred Submittal) Express REQUIRES RESUBMIT Submit Masonry reports
10/21/2025 Other Inspection Reports (Deferred Submittal) Express REQUIRES RESUBMIT Submit fabricator reports

FABRICATORS
10/21/2025 Post-Installed Anchor Inspection (Deferred Submittal) Express REQUIRES RESUBMIT Submit post installed anchor reports
10/21/2025 Air Balancing/Commissioning Report (Deferred Submittal) Express REVIEW COMPLETED
10/17/2025 PDSD Application Completeness Express REVIEW COMPLETED