Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0225-00263
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/25/2025 | Commercial Electrical Standard | APPROVED | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved with Comments Reason: Date Completed : 2/20/2025 6:48:00 PM 1. E1B201: Should call out number and conductor size of new conductors for all Keynote 3 locations. 2. E10302: Keynote 1 should be clarified or broken into two Keynotes. 3. E10404: Should call out number and conductor size of new conductors for all Keynote 1 locations. 4. E10405: Keynotes 4 & 5 also incorrectly shown elsewhere on sheet. Should correct. |
||
| 02/25/2025 | Commercial Mechanical Standard | APPROVED | Mechanical(M) Reviewer Jorge Valido jvalido@safebuilt.com Approved Reason: Date Completed : 2/17/2025 12:45:53 PM |
||
| 03/05/2025 | Water - PDSD Standard | APPROVED | |||
| 03/12/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/25/2025 | Commercial Building Standard | REQUIRES RESUBMIT | Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Denied Reason: Date Completed : 2/25/2025 3:32:52 PM 1. GENERAL - UPDATES: For project updates, please submit sheets with all changes clearly marked in revision clouds. Please provide a written response to each comment; updates without a clear response to all comments may not be reviewed. If you have any questions regarding the comments, you may contact me directly. Updates may result in additional comments. 2. GENERAL - FIRM REGISTRATION: Per the Arizona Revised Statutes, Chapter 32, Rule 141, a firm shall not engage in the practice of any board-regulated profession or occupation unless the firm is registered with the board”. The Engineer of Record, Complete Project Solutions, carries a firm registration that has expired. Prior to permit approval, their firm registration must be brought up to date. Refer to the Arizona State Board of Technical Registration (https://btr.az.gov/public/registered-firm-branch-search) for more information. 3. GENERAL - SPECIAL INSPECTIONS: Please have the Registered Design Professional in Responsible Charge of this project complete and return the City of Tucson Special Inspections Certificate with signatures. The form can be downloaded at: https://www.tucsonaz.gov/files/sharedassets/public/city-services/planning-developmentservices/documents/special_inspection_certificate.pdf 4. SHEET S1.0 - STATEMENT OF SPECIAL INSPECTIONS: The structural general notes do not fully describe the required special inspections for field welding as outlined in the AISC 360 Chapter N. Refer to the 2018 International Building Code Section 1704.3.1, for a full list of what a Statement of Special Inspections is required to include. Highlights from the code include: i. Statement shall identify the materials and work required to have special inspections or tests, ii. The type and extent of each inspection, and iii. Identification as to whether each inspection shall be performed continuously or periodically, as defined by the IBC. Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : 2/13/2025 12:26:33 PM |
||
| 02/25/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 2/22/2025 4:18:27 PM First Plumbing Review: 1). Plumbing Plans All pages: The 3" drain pipe sizes shown on plan page P10301 don't correlate with the 4" outlet floor sink shown on plan page P001. Update plans to correlate with fixture outlets & pipe sizes. -2018 IPC 704.2 2). Plan Page P001 fixture schedule: Missing trap primer for floor sink. Add trap primer or trap guard for floor sink. -2018 IPC 1002.4.1 |
||
| 03/05/2025 | Design Review Standard | REQUIRES RESUBMIT | This property is located within the boundaries of the Rio Nuevo Area (RNA), with the structure onsite designated as contributing to the Downtown Tucson National Register Historic District. If the proposed improvements are visible from the ROW, a Design Package will need to submitted as a subrecord of TC-COM-0225-00263, demonstrating compliance with the requirements of the RNA and historic preservation standards, as specified in the Unified Development Code (UDC) Section 5.12.7. Please provide dimensioned north, east, and west elevations of the building, with the heights of the new equipment, to be able to determine the applicability of the RNA. Here's an overview of the RNA: https://www.tucsonaz.gov/files/sharedassets/public/v/3/pdsd/documents/planning-amp-zoning/rna-application-and-review-process.pdf. If you have any questions, please let me know: maria.gayosso@tucsonaz.gov. Thank you. | ||
| 03/05/2025 | Historic Standard | REQUIRES RESUBMIT | This property is located within the boundaries of the Rio Nuevo Area (RNA), with the structure onsite designated as contributing to the Downtown Tucson National Register Historic District. If the proposed improvements are visible from the ROW, a Design Package will need to submitted as a subrecord of TC-COM-0225-00263, demonstrating compliance with the requirements of the RNA and historic preservation standards, as specified in the Unified Development Code (UDC) Section 5.12.7. Please provide dimensioned north, east, and west elevations of the building, with the heights of the new equipment, to be able to determine the applicability of the RNA. Here's an overview of the RNA: https://www.tucsonaz.gov/files/sharedassets/public/v/3/pdsd/documents/planning-amp-zoning/rna-application-and-review-process.pdf. If you have any questions, please let me know: maria.gayosso@tucsonaz.gov. Thank you. | ||
| 03/12/2025 | Site Engineering Standard | REQUIRES RESUBMIT | TC-COM-0225-00263 126 E ALAMEDA ST 1. As this site is located within the Downtown Core and RNA, Historic and Design Review Standards must be approved prior to Engineering approval. |
||
| 03/04/2025 | Site Zoning Standard | REQUIRES RESUBMIT | FROM: PDSD Zoning Review Section PROJECT: TC-COM-0225-00263 126 E ALAMEDA ST. - OCR-2 Cooling Tower Replacement (1st Review) TRANSMITTAL DATE: March 4, 2025 COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the OCR-2 zone (UDC 4.7.27). Telephone Distribution is an approved use in the zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.11.A.1, .5, & .9. 1. As this site is located within the Downtown Core and RNA, Historic and Design review must be approved prior to Zoning approval. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
| 02/14/2025 | Fire New Construction Standard | REVIEW COMPLETED | Any alterations or additions to the fire alarm and fire sprinklers systems requires a new submittal and permit. | ||
| 02/11/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |