Permit Number: TC-COM-0224-00338
Parcel: 14041124C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0224-00338
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
05/07/2024 External Reviewers - Stantec REQUIRES RESUBMIT April 9, 2024
2nd Review

a23 Studios
Attn: Shawn Curtis
711 E. 9th Street
Tucson, Arizona 85719

Re: MICROSTAR
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0224-00338
Stantec Project Number: 185215066
Stantec File Number: TUC-24-019

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B
V-B 13,750
391
Yes
No
F-2 92,828
S-2 7,394
Separate Permits: Automatic fire sprinklers
Deferred Submittals: Racking system.
Special Inspections: Epoxy and expansion anchors, structural steel, high-strength bolts, field welding.

ARCHITECTURAL COMMENTS

General

1. Addressed.

2. Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors, structural steel, high-strength bolts, field welding. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Still Required: The special inspection certificate was not provided with the latest submittal. Please provide.

3. Addressed.

Sheet A0.1

1. Addressed.

2. Please provide fixture calculations indicating the minimum number of required fixtures for the proposed uses in accordance with Table 2902.1 of the 2018 International Building Code. Still Required: The code analysis does not reflect the plumbing fixture calculations in compliance with T2902.1. Please provide.

Sheet A2.1

1. Addressed.

Sheet A8.0

1. Addressed.

STRUCTURAL COMMENTS

Sheet 2.0

1. Addressed.

MECHANICAL COMMENTS

Sheet M2.1

1. Addressed.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

Sheet E2.1

1. Addressed.

Sheet E4.1

1. Addressed.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com