Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0224-00316
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/13/2024 | Commercial Building | APPROVED | |||
03/13/2024 | Commercial Electrical | APPROVED | |||
03/18/2024 | Water - PDSD | APPROVED | |||
03/18/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
03/18/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Footnote g, Table 403.3.1.1, IMC 2018, calls for public restrooms to be mechanically exhausted. Show how this will be provided. Reference: Section 403.2.1 (4), IMC 2018. | ||
03/18/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Provide cleanouts at the junctions of the building drains and the building sewer. Reference: Section 708.1.3, IPC 2018. | ||
03/07/2024 | Historic | REQUIRES RESUBMIT | The property is a contributing resource to the West University Historic Preservation Zone and requires review and approval. Please provide documents noted under Full Review in the Historic & Special Districts informational handout (https://www.tucsonaz.gov/files/sharedassets/public/v/3/pdsd/documents/submission-documents/special_districts_application_instructions_7.18.23.pdf) and submit under the Historic sub-record. Questions? Jodie.Brown@tucsonaz.gov | ||
03/07/2024 | Site Engineering | REQUIRES RESUBMIT | See zoning comments | ||
03/05/2024 | Site Zoning | REQUIRES RESUBMIT | FROM: PDSD Zoning Review Section PROJECT: TC-COM-0224-00316 941 N 4TH AV. – HR-2 Remodel existing restroom (1st Review) TRANSMITTAL DATE: March 5, 2024 COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8). This site is located in the HR-2 zone (UDC 4.7.9). Parks and Recreation is an allowed use in the zone (UDC Table 4.8-2), subject to Use Specific Standards 4.9.13.B & C. 1. Until approved by Historic Zoning cannot approve this plan. Historic Review is required. Please submit a special districts application as a sub-record of this permit. The submittal requirements and instructions can be found below. Please contact Jodie Brown (jodie.brown@tucsonaz.gov) or Michael Taku (michael.taku@tucsonaz.gov) for any questions. Zoning can not approve until the historic review has been approved. https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/planning-amp-zoning/special_districts_application_instructions-1.pdf 2. Zoning cannot approve the building plans until Development Package (DP) TD-DEV-0224-00028 is approved by all review agencies. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
02/26/2024 | Fire New Construction | REVIEW COMPLETED | |||
02/26/2024 | PDSD Application Completeness | REVIEW COMPLETED |