Permit Number: TC-COM-0224-00302
Parcel: 125120810

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0224-00302
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2024 Commercial Building APPROVED
05/28/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
05/23/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 This lighting plan submittal shows new exterior lighting not shown in the previous submittal..

Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements.

1. Provide site lighting plans with the following information on the plans;

(a) Provide a complete luminaire schedule.

(b) Full compliance with sections 104.2.1(1), (2), (3).

2 See table 401.1, Include parcel size, lighting area and option, and indicate this information in the lighting site plan.

3 402.1 (light source color temperature requirements, 3500K), shielding requirements, etc .

4 Provide calcs for total lumens allowed and total lumens proposed per acre for Full Cut Off and Unshielded per table 401.1.Must include existing to remain lighting.

5 Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

6 Specify any exceptions used.

7 Provide Curfew lighting controls If applicable Per section 403.

8 Provide complete compliance with the 2018 IECC for the interior and exterior lighting where applicable.

Do not confuse the Outdoor Lighting Code with the IECC.

Ref; 2012 City of Tucson Outdoor Lighting Code .
05/28/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Ventilation calculations (Zone Outdoor Air Provided, Supply Air Design) do not agree with the Rooftop Unit Schedule. [Initial comment: Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018.]
2. The architect shows the kitchen area to be in excess of 500 square feet. Based on 100 square feet per cooking appliance (TurboChef oven, 2 microwave ovens), an exhaust flow rate of at least 210 CFM is required. [Initial comment: EF-3 appears to be providing general room exhaust for the kitchen. General room exhaust is required for cooking appliances that do not require the installation of a Type I or a Type II hood. The minimum exhaust rate for this application is 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. What is the basis for the exhaust flowrate for EF-3? Reference: Section 507.1, exception 2 and 507.3, IMC 2018.]
05/28/2024 Commercial Plumbing REQUIRES RESUBMIT 1. The Backflow Assembly Requirements Schedule shows ASSE 1070 as standard for the reverse pressure backflow preventer, it should be ASSE 1013. [Initial comment: Clarify the purpose of the backflow preventer, BFP-1, If it is intended to protect the municipal water distribution system from the water use in the building, it must be installed in a location accessible to Tucson Water, typically adjacent to the utility water meter. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf.].
2. The mop sink and prep sink are discharging to sanitary waste. They are required to discharge to the grease interceptor. [Initial comment: Coordinate the waste plumbing plan, 2/P2-01, with the overall plumbing plan, 1/P2-01 by including all of the proposed plumbing fixtures. Reference: Section 107.2.1, IBC 2018.]
3. Clarify the installation of the grease interceptor. Detail 3/P1-01 shows it located below the floor, keynote 2 on P2-01 calls for it to be above the floor, and the Overall Plumbing plan shows it located below the restroom wall. [Initial comment: Provide a vent downstream of the gravity grease separator to protect the seal for the grease separator. Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson.]
4. Revise the new floor drain in restroom 109 to show the connection to the horizontal drain from the mop sink and hand sink flowing in the correct direction. Reference: Section 706.3, IPC 2018.
05/21/2024 Site Engineering REQUIRES RESUBMIT The building permit cannot be approved until the associated floodplain use permit, TE-FPU-0324-00075, has been issued.

Lianne Evans
lianne.evans@tucsonaz.gov
04/24/2024 PDSD Application Completeness REVIEW COMPLETED