Permit Number: TC-COM-0224-00302
Parcel: 125120810

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.2

Permit Number - TC-COM-0224-00302
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/01/2025 Air Balancing/Commissioning Report (Deferred Submittal) Express REQUIRES RESUBMIT The document is NOT an air balance report. The air balance report was approved on 03/12/2025. The submitted document only shows that a water sample was delivered to Turner Laboratories on 3/13/25. Provide the complete water sample analysis report from Turner Laboratories.
04/10/2025 County Health Inspection (Deferred Submittal) Express REQUIRES RESUBMIT Please submit an Approved Inspection report. The one submitted dated 02.05.2025 shows as 'Not Approved'.
03/28/2025 PDSD Application Completeness Express REVIEW COMPLETED