Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0224-00294
Parcel: 12905130U

Address:
2111 E 17TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0224-00294
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2024 Commercial Electrical APPROVED
03/20/2024 Commercial Mechanical APPROVED
03/20/2024 Water - PDSD APPROVED
03/20/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/20/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Verify the specified tankless water heater. Eemax does not list an EX35127 model; they do however list an EX3512T model. Reference: Section 107.2.1, IBC 2018.
2. Verify that hot water source is within 24” of the lavatory connection. Reference: Section C404.5, IECC 2018.
03/15/2024 Commercial Structural REQUIRES RESUBMIT Please submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed.
1. Please amend plans to show compliance with IBC Table 602 requiring a minimum 10- foot Fire Separation Distance (FSD) for V-B exterior walls with a 0-hour fire-resistance rating. If the building was positioned to be 20 feet away from the existing building with an imaginary showing a 10-foot FSD for each building, this would work. IBC 602.1
2. Please provide a Statement of special inspections. IBC 1704.2.3
3. Please add Metal Building plans for construction to the deferred submittal list, as the drawing that were submitted were marked as not for construction. IBC 107.3.4.1

Mark Masek
Plans Examiner
Mark.masek@tucsonaz.gov
520-837-4994
03/14/2024 Site Engineering REQUIRES RESUBMIT See zoning comment
03/13/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: Wyatt Berger
Lead Planner

PROJECT: TC-COM-0224-00294
2117 East 17th Street – I-1
Detached storage building (1st Review)

TRANSMITTAL DATE: March 13, 2024

Please resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed.

1. Zoning has reviewed the building plans for compliance with associated development package TD-DEV-0223-00139. Although it appears the building plan footprint, building height, and square footage are consistent with the submitted development package, Zoning cannot approve TC-COM-0224-00294 until the revision to TD-DEV-0223-00139 is approved.

If you have any questions about this transmittal, contact me at Wyatt.Berger@tucsonaz.gov or at 520-837-4951.
02/16/2024 Fire New Construction REVIEW COMPLETED
02/13/2024 PDSD Application Completeness Express REVIEW COMPLETED