Permit Number: TC-COM-0224-00275
Parcel: 10821328B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0224-00275
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2024 Commercial Plumbing APPROVED
02/27/2024 Site Zoning APPROVED
03/18/2024 Water - PDSD APPROVED
03/05/2024 Site Engineering NOT REQUIRED
03/18/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
03/12/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Provide for secondary light reduction controls or occupancy sensors in the offices as required per the 2018 IECC section C405.2, C405.2.1.3.

2 Provide receptacle placement in the conference rooms as required per NEC art 210.71.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC.
03/18/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Show that the proposed replacement rooftop units meet the requirements of Sections C403.3, C403.4, and C403.5 (e.g. provide the mechanical compliance certification from COMcheck). Reference: Section C501.4, International Energy Conservation Code 2018.
2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
3. Provide structural calculations and details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2018.
03/15/2024 Commercial Structural REQUIRES RESUBMIT Please submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed.
1. Sheet A1.0: Please resolve this apparent discrepancy; the address on the Code Analysis and the Reference Only Site Plan do not match the address in the Title block or the permit. IBC 107.2.1

2. Sheet A1.0: Please amend plans to provide a more detailed description of the work involved in this permit’s scope. IBC 105.3. For example, Tenant Improvement created suite 300 and suite 3##. From existing suite 3##. Demolition to include…existing mechanical and electrical and plumbing work, interior walls, except existing demising wall and a portion of the existing storefront to allow the installation of a new exit door. New work to include new demising wall between suite 300 and 3##.........................................................................................etc.

3. Sheet A1.0: Please provide the suite numbers for both spaces. IBC 107.2.1

4. Sheet A1.0: Please amend General Building Summary to indicate which story this project is on as the actual building height is listed as two stories; however, the Reference Only Site Plan and the suite numbers give the impression the project is on the third floor. IBC 107.2.1

5. Sheet D1.0 Please amend plans to indicate the wall type of the existing exterior wall to be demoed for new door 101A. IBC 107.2.1

6. Sheet A1.1: Please amend plans to show the number of occupants, the load factor and area of every room and space. IBC 107.2.3, IBC 1004.5

7. Sheet A1.1: Please amend plans as they appear to show a dead-end corridor on the egress balcony from door 114B to the stairway. Balconies used for egress purposes shall conform to the same requirements as corridors for minimum width, required capacity, headroom, dead-ends, and projections. IBC 1021.1

8. Sheet A2.0: Please amend plans to provide a drawing or if only the exterior finish is different please add note to detail showing how the door opening for 101A is to be constructed and finished as it appears to be a different wall type. For example, an exterior wall and not a partition wall. IBC 107.2.1

9. Sheet A3.0: Please amend plans to show the ceiling heights of all areas. IBC 1003.2

Mark Masek
Plans Examiner
Mark.masek@tucsonaz.gov
520-837-4994
03/04/2024 Fire New Construction REVIEW COMPLETED
02/09/2024 PDSD Application Completeness REVIEW COMPLETED