Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.2
Permit Number - TC-COM-0224-00239
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/18/2024 | Commercial Building | APPROVED | |||
| 03/18/2024 | Commercial Electrical | APPROVED | |||
| 03/18/2024 | Commercial Plumbing | APPROVED | |||
| 03/18/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/18/2024 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Revise the ventilation calculations to include the Zone Air Distribution Effectiveness (Table 403.3.1.1.1.2, IMC 2018) and the System Ventilation Efficiency (Section403.3.1.1.2.3.2, IMC 2018). (The outside air balancing note for AC #1 is correct.) [Initial comment: Calculation of the required minimum ventilation for air handlers serving multiple zones requires the balancing data (supply CFM) for each zone and the calculations described in Sections 403.3.1.1.2.3.1 through 403.3.1.1.2.3.4, IMC 2018. Reference: Section 403.3.1.1.2.3, IMC 2018.] 2. Revise the balancing data for EF #2 on the mechanical plan to agree with the exhaust quantities noted in the ventilation calculations. [Initial comment: Revise the exhaust airflow rate for the cutting floor and shampoo area to provide 0.5 CFM of exhaust per square foot. (Note that a barber shop only requires 7.5 CFM of outside air per person and 0.06 CFM of outside air per square foot.) Reference: Section 403.3.1.1, IMC 2018.] |
||
| 03/15/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |