Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-0224-00239
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/28/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/28/2024 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | Exhaust fan EF#2 is not operational. The balancing data for EF #2 noted on the mechanical plan is incorrect. The exhaust quantities noted in the ventilation calculations, 289 CFM are correct, not the 129 CFM shown on the air balance report. Reference: Section 403.3.1.1, IMC 2018. | ||