Permit Number: TC-COM-0224-00239
Parcel: 14118629A

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TC-COM-0224-00239
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/28/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/28/2024 Air Balancing/Commissioning Report (Deferred Submittal) Express REQUIRES RESUBMIT Exhaust fan EF#2 is not operational. The balancing data for EF #2 noted on the mechanical plan is incorrect. The exhaust quantities noted in the ventilation calculations, 289 CFM are correct, not the 129 CFM shown on the air balance report. Reference: Section 403.3.1.1, IMC 2018.
05/24/2024 PDSD Application Completeness Express REVIEW COMPLETED