Permit Number: TC-COM-0223-00714
Parcel: 13213104B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0223-00714
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
06/14/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0223-00714

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 6/14/2023 8:42:05 AM
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.

Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 6/13/2023 12:54:41 PM
1. The pre-engineered metal building shop drawings have not been provided for this submittal. Provide a complete set of the pre-engineered metal building shop drawings from the manufacturer.

Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 6/12/2023 5:55:59 PM
Electrical Review
By: Ron Ross PE
ESH.3 PANEL SCHEDULES, ONLE LINE DIAGRAM AND CALCS: Comment only. May want to confirm or possibly have the Utility provide more than 4 sets of feeders to the SES as indicated by Cable from Fault current analysis.

Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 6/12/2023 10:14:06 PM
Second Plumbing Review:
1). SAME-Plans need to be accompanied by civil utility plan as stated on plan page P1.0 for continuation sewer & water service -IPC 106.3.1 ** The Site development package that was included was only partial & did not include utility pages, only storm**
06/08/2023 PDSD Application Completeness REVIEW COMPLETED