| 07/13/2023 | Fire New Construction | REQUIRES RESUBMIT | Revised comments. Removed the elevator comment from previous review. -IFC 1009.8. Two way communication shall be provided at the elevator landing other than the landing at the level of exit discharge. Add two way communications to the drawings or indicate it will be part of the FA deferred submittal. -Sheet E3.0 indicates the building will be tested for ERRC. This is not required unless the bldg is over 35'. You can leave the note if you plan on testing the building or remove the note. If you leave the note, bldg will need to be tested by PCWIN for radio coverage. john.vincent@tucsonaz.gov 5203495581 |