Permit Number: TC-COM-0223-00705
Parcel: 11310001A

Address:
1545 E COPPER ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0223-00705
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2023 External Reviewers - Stantec APPROVED
03/07/2023 Site Engineering APPROVED
03/24/2023 Site Zoning APPROVED
07/07/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/05/2023 Fire New Construction REQUIRES RESUBMIT -Elevator shall comply with IFC 1009.4.1 for standby power.
-IFC 1009.8. Two way communication shall be provided at the elevator landing other than the landing at the level of exit discharge. Add two way communications to the drawings or indicate it will be part of the FA deferred submittal.
-Sheet E3.0 indicates the building will be tested for ERRC. This is not required unless the bldg is over 35'. You can leave the note if you plan on testing the building or remove the note. If you leave the note, bldg will need to be tested by PCWIN for radio coverage.
03/06/2023 PDSD Application Completeness Express REVIEW COMPLETED