Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2023 Site Zoning APPROVED
03/20/2023 Site Engineering NOT REQUIRED
03/29/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
03/29/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0223-00664

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. New 7 Condensing Units HP-1 thru HP-7 weighing up to 292 pounds, one Outdoor Unit ODU-1 weighing 93 pounds and a Fan weighing 29 pounds is added at existing roof (Refer to Drawings M-101, M-201 and A-530). Provide Structural Calculations for the Roof Supporting members checking their adequacy to carry additional loads from these new units.
2. All Calculations shall be sealed and signed by Professional Engineer registered with State of Arizona per Section 107.1 of International Building Code 2018.
Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Denied
1. Where duct penetrates more than 2 stories it shall be protected by a shaft for the bathroom exhaust on sheet M-100 separation between B & E occupancy in table 508.4 of the IBC requires a 1 hour separation (IMC2018,607.6.1)
2. Appliances installed on roof's above 16" from grade shall be provided with an approved permanent means of access sheet M-101 (IMC2018306.5)
3. on your ventilation outside air schedule for room #108 you got required outside airflow at 283 cfm's but AHU-1 is only bringing in 240cfm's.
also the total air required for AHU-2 total required air is 222cfm and your only bringing in 205cfm's
also AHU-4 required is 320 cfm's your only bringing in 300 cfm's
please correct pm sheet M-201 (IMC2018,403.3.1.1.1)


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
FYI for future submittals for Tucson: Tucson require’s short circuit calculations for panels to confirm that KAIC ratings are sufficient for new panels.
This review is approved as Panel's were spec'd at 22 KAIC, a value 2x higher than standard 240 VAC rated panels.


PLUMBING REVIEW COMMENTS:
Denied
First Plumbing Review:
1). Provide the water piping sizing calculations used on plan page P-100 to show the 3/4" cold is sufficient for distance & all the fixtures shown. -IPC 604.1


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
03/21/2023 Fire New Construction REVIEW COMPLETED
03/10/2023 PDSD Application Completeness REVIEW COMPLETED