Permit Number: TC-COM-0223-00654
Parcel: 133231470

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0223-00654
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/30/2023 Site Zoning APPROVED
03/30/2023 Site Engineering NOT REQUIRED
04/03/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
03/27/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0223-00654


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


BUILDING REVIEW COMMENTS:
Denied
1. Sheet G003: The plan provided on the indicated egress sheet is not an egress plan. Provide detailed egress plans that show the new proposed layout.
2. Sheet G003: No code analysis has been provided. Provide a Building Code Data Legend on the Title Sheet. Include the following code information for each building proposed:
◦ Occupancy Classification(s)
◦ For Mixed Occupancy Buildings, state whether the “non-separated” or “separated” option was chosen from Sections 508.3 / 508.4.
◦ Description of Use
◦ Type of Construction
◦ Sprinklers:
◦ Stories
◦ Height
◦ Floor Area (both the the existing and affected area)
◦ Occupant Load (UPDATED)
3. Multiple Sheets: The door schedules provided on each phased sheet do not match the doors on that particular phase. Provide update door schedule for each individual phase.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E101 PHASE 01 ELECTRICAL PLANS LIMITED SCOPE: Could not locate Keynote #1.
E102 PHASE 02 ELECTRICAL PLANS LIMITED SCOPE: Could not locate Keynote #1.
E103 PHASE 03 ELECTRICAL PLANS LIMITED SCOPE: Could not locate Keynote #1.
E104 PHASE 04 ELECTRICAL PLANS LIMITED SCOPE: Could not locate Keynote #1.
E105 PHASE 05 ELECTRICAL PLANS LIMITED SCOPE:
Could not locate Keynote #1.
Keynote #2 last two words ‘AN Downer’ should be corrected. Comment applies to other sheets too.
E108 PHASE 08 ELECTRICAL PLANS CONSTRUCTION: Could not locate Keynote #1.
E109 PHASE 09 ELECTRICAL PLANS CONSTRUCTION: Could not locate Keynote #1.
E114 PHASE 14 ELECTRICAL PLANS LIMITED SCOPE: May need a comment about removing power from office cubicles.


PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
04/03/2023 Fire New Construction REVIEW COMPLETED
03/09/2023 PDSD Application Completeness REVIEW COMPLETED