Permit Number: TC-COM-0223-00646
Parcel: 132131420

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.6

Permit Number - TC-COM-0223-00646
Review Name: COMMERCIAL REVIEW - FULL v.6
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2023 Bldg Permits - Post Review REVIEW COMPLETED
11/02/2023 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 7/14/2023 1:31:24 AM



Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 7/14/2023 1:31:01 AM




Mechanical(M) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 3/18/2023 1:05:38 AM



Electrical(E) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 7/14/2023 1:31:12 AM



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 11/1/2023 9:46:38 PM
Fifth Plumbing Review: OK Subject to field inspections
1). OK
2). OK
3). Resolved-Plan page P1.0 needs to include Roof drain Primary & secondary Storm conductor illustrations, routing, sizing, termination points, sizing calculations GPM loads -IPC 106.3.1, 1106.2, 1108,
4). OK
5). OK-revised plan page A5.1 roof drain calculations need to derive from IPC 2018 section 1106.2, not IPC 2015 1106.3**Correct Rainfall rain rate per Tucson Amendments shown on plan page P1.0 notes 2 & 3**
10/30/2023 PDSD Application Completeness REVIEW COMPLETED