Permit Review Detail
Review Status: Approved
Review Details: COMMERCIAL REVIEW - FULL v.6
Permit Number - TC-COM-0223-00646
Review Name: COMMERCIAL REVIEW - FULL v.6
Review Status: Approved
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/02/2023 | Bldg Permits - Post Review | REVIEW COMPLETED | |||
11/02/2023 | External Reviewers - SAFEBuilt | REVIEW COMPLETED | Structural(S) Reviewer Janet Matz jmatz@safebuilt.com Approved Reason: Date Completed : 7/14/2023 1:31:24 AM Building(B) Reviewer Janet Matz jmatz@safebuilt.com Approved Reason: Date Completed : 7/14/2023 1:31:01 AM Mechanical(M) Reviewer Janet Matz jmatz@safebuilt.com Approved Reason: Date Completed : 3/18/2023 1:05:38 AM Electrical(E) Reviewer Janet Matz jmatz@safebuilt.com Approved Reason: Date Completed : 7/14/2023 1:31:12 AM Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Conditionally Approved Reason: Date Completed : 11/1/2023 9:46:38 PM Fifth Plumbing Review: OK Subject to field inspections 1). OK 2). OK 3). Resolved-Plan page P1.0 needs to include Roof drain Primary & secondary Storm conductor illustrations, routing, sizing, termination points, sizing calculations GPM loads -IPC 106.3.1, 1106.2, 1108, 4). OK 5). OK-revised plan page A5.1 roof drain calculations need to derive from IPC 2018 section 1106.2, not IPC 2015 1106.3**Correct Rainfall rain rate per Tucson Amendments shown on plan page P1.0 notes 2 & 3** |
||
10/30/2023 | PDSD Application Completeness | REVIEW COMPLETED |