Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.4
Permit Number - TC-COM-0223-00641
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/21/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/20/2023 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Activity Number: TC-COM-0223-00641 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. Structural(S) Reviewer Daljit Benipal dbenipal@safebuilt.com Conditionally Approved Reason: Date Completed : 6/19/2023 6:49:32 PM NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances. Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : 6/15/2023 10:52:00 AM Mechanical(M) Reviewer Neil Samaan nsamaan@safebuilt.com Conditionally Approved Reason: Date Completed : 4/30/2023 10:51:25 PM Approved/subject to field approval Electrical(E) Reviewer Ron Ross rross@safebuilt.com Conditionally Approved Reason: Date Completed : 3/16/2023 9:34:05 AM Electrical Review By: Ron Ross PE E2.0 First Floor Lighting Plan: Could not locate Keynote 4. Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 6/18/2023 8:39:26 PM Third Plumbing Review: 1). OK 2). SAME-what is preventing AD1 on plan page P2.0 from receiving storm water from exterior grade? -IPC 1101.3 ( Plan Page A5.0 shows open exterior grade at same level as covered slab & plan page S2.0 shows slab pitching to drain.) 3).OK 4). OK. 5). Added vent for AD1 on plan page P2.0 must rise 6" above the drain being served before offsetting horizontally. -IPC 905.4, 905.5 |
||
| 06/21/2023 | Site Engineering | REQUIRES RESUBMIT | See Zoning Comment | ||
| 06/12/2023 | Site Zoning | REQUIRES RESUBMIT | FROM: Paul Camarena PDSD Zoning Review Section PROJECT: TC-COM-0223-00641 3381 E WESTCO PL Zoning I-1 TRANSMITTAL DATE: June 12, 2023 COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This comment is still applicable. 1.COMMENT: Zoning has reviewed the building plan for compliance with TD-DEV-0223-00138 and although it appears that the building plans match the DP Zoning cannot approve the building plans until the DP is approved. If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov |
||
| 06/07/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |