| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/03/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/03/2023 | Commercial Mechanical | REQUIRES RESUBMIT | The odor control letter, submitted 07/05/2023, calls for the addition of activated charcoal filters and UV-C lights to be added to “all air returns throughout the facility.” Provide a design for this modification of the HVAC system, including equipment specifications and the required modifications to the electrical distribution system. An air balance report will be required to ensure that increased pressure drop in the HVAC system does not adversely affect the ventilation requirements. Reference: Section 107.2.1, IBC 2018. | ||