Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0223-00617
Parcel: 132166250

Address:
4850 S PARK AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0223-00617
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/03/2023 Commercial Mechanical REQUIRES RESUBMIT The odor control letter, submitted 07/05/2023, calls for the addition of activated charcoal filters and UV-C lights to be added to “all air returns throughout the facility.” Provide a design for this modification of the HVAC system, including equipment specifications and the required modifications to the electrical distribution system. An air balance report will be required to ensure that increased pressure drop in the HVAC system does not adversely affect the ventilation requirements. Reference: Section 107.2.1, IBC 2018.
07/05/2023 PDSD Application Completeness Express REVIEW COMPLETED