Permit Number: TC-COM-0126-00138
Parcel: 12108284A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0126-00138
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2026 Commercial Building Standard APPROVED
02/03/2026 Commercial Electrical Standard APPROVED
02/18/2026 Site Zoning Standard APPROVED
02/10/2026 Water - PDSD Standard APPROVED
02/17/2026 Site Engineering Standard NOT REQUIRED
02/18/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/10/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0126-00138
ADDRESS/PARCEL: 6246 E PIMA ST Unit:UNIT 180 TUCSON, AZ 85712

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Provide information on the sequence of operation for the restroom exhaust fan to show that all of the air supplied to the restroom will be exhausted. Reference: Section 403.2.1 (4), IMC 2024.
02/10/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0126-00138
ADDRESS/PARCEL: 6246 E PIMA ST Unit:UNIT 180 TUCSON, AZ 85712

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Please show that the distance from the hot water source (i.e., the recirculating loop) to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2024.
2. The metering faucet shall dispense a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds for accessibility. Reference: Section 412.13, IPC 2024, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
02/17/2026 Fire New Construction Standard REVIEW COMPLETED
02/03/2026 PDSD Application Completeness Express REVIEW COMPLETED limited scope TI timeline