Permit Number: TC-COM-0126-00131
Parcel: 13213075B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0126-00131
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2026 Commercial Electrical APPROVED
02/03/2026 Outdoor Lighting APPROVED
02/18/2026 Site Zoning NOT REQUIRED Charter School is exempt from Site Zoning review however a Development Package will still be required for additional site reviewers.
02/18/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/02/2026 Addressing Validation REQUIRES RESUBMIT If you have questions regarding the Addressing Validation Review, please contact Maribel Arevalo at maribel.arevalo@tucsonaz.gov
The project address on the building application does not match the address on the permit application (the permit application lists bldg 1 and the plans do not). If this project is part of building 1, please add building 1 to your plans and resubmit. If this project should not list unit 1, please remove building 1 from your permit application address by submitting a Request Change of Address; How to submit a Change of Address:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/withdraws-and-extensions.pdf
Then resubmit plans; Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf
02/12/2026 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Please provide dimensioned construction drawings for the shade structure. IBC 107.2.1
2. Please provide a scaled architectural site plan is provided showing all buildings or structures on the lot. IBC 107.2.6 Additionally, provide the following on the site plan.
A. A north arrow and adjacent street names. IBC 107.2.1
B. Dimensioned distances between structures and adjacent lot lines. IBC 107.2.6
C. Dimensioned distances between structures and the centerline of directly adjacent public ways. IBC 602.1
D. Dimensioned distances between structures and a shown imaginary line between adjacent buildings on the same lot. IBC 602.1
3. Please amend the plans to list the year and name of the adopted applicable codes from the adopting ordinance. IBC 107.2.1 Starting January 1st, the 2024 I codes are the governing codes, with the exception of the IECC which is still the 2018 edition.
4. Please amend the plans to show the accessible route to the stage. IBC 1104.2
A. Please provide construction drawings in compliance with 2024 IBC Section 1012 if a ramp is used.
5. Please amend the plans to provide the following information for the Stairways, handrails.
A. Details are provided for the construction information for all stairs and landings. IBC 1011.1
B. 7” max risers, 11” min treads, landings, handrail each side. IBC 1011
C. Nosing projection above the tread below is a maximum of 1 ΒΌ inches. IBC 1011.5.5.1
D. Details are provided for the construction information for all handrails and guards. IBC 1014.1, 1015.1
E. Handrails return to walls, are continuous, and extend where not continuous. IBC 1014.6
F. Handrails are graspable and continuous except for brackets extending down 1.5 inches. 1014.3, 1014.4
6. Provide the signed and sealed structural calculations, prepared by an Arizona licensed registrant, used in the design of this project. IBC 107.2.77.
7. Please provide a project specific statement of special inspections for this project, stating requirements for the special inspections and required tests. IBC 107.2.1, IBC 1704, IBC 1705
Additionally, provide the City of Tucson Special Inspection Certificate(s) with Parts A and B
completed with the next submittal. IBC 107.1 SI form link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf

Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
02/17/2026 Site Engineering REQUIRES RESUBMIT Site Engineering Review

TC-COM-0126-00131
3300 S PARK AV Unit: 1

Summary: New flatwork and shade structure in the courtyard between two buildings.

Site Engineering comments are as follows:

1. This proposed Commercial Building Permit, TC-COM-0126-00131, will require a Development Package that complies with the criteria found in Administrative Manual 2-06.4.0 thru 2-06.4.9. This is a separate permit submittal. The Building Permit and the Development Package may be submitted at the same time, and their reviews may run concurrently, however, the Development Package must be approved by all reviewers prior to the approval and issuance of the Building Permit.
2. Please follow this link to the TDC Online Portal to submit a development package permit application and re-submit this permit.

To re-submit, visit the Tucson Development Center Online at:
https://tdc-online.tucsonaz.gov/#/home

The instructions for resubmittal can be found at: Revisions and Resubmittals

Engineering Associate: Ryan Insalaco
ryan.insalaco@tucsonaz.gov
02/13/2026 Fire New Construction REVIEW COMPLETED
02/02/2026 PDSD Application Completeness Express REVIEW COMPLETED This permit will be for the shade structure not attached to building 1. The structure attached to building 1 will require a separate permit.