Permit Number: TC-COM-0126-00049
Parcel: 141185950

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-0126-00049
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/06/2026 Commercial Building Standard APPROVED
04/06/2026 Commercial Electrical Standard APPROVED
04/02/2026 Commercial Mechanical Standard NOT REQUIRED
04/02/2026 Site Zoning Standard NOT REQUIRED
04/02/2026 Water - PDSD Standard NOT REQUIRED
04/06/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/02/2026 Commercial Plumbing Standard REQUIRES RESUBMIT The fixture drains of two fixtures located on the same floor level may be connected to a common vent on different levels, but the upper fixture shall not be a water closet. Reference: Sections 911.1 and 911.3, IPC 2024.

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
04/01/2026 Fire New Construction Standard REVIEW COMPLETED
03/24/2026 PDSD Application Completeness Express REVIEW COMPLETED