Permit Number - TC-COM-0126-00047
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/14/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/14/2026 | Commercial Electrical Express | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0126-00046 (2333 E GLENN ST Unit:UNIT 102 TUCSON, AZ 85719) TC-COM-0126-00014 (2333 E GLENN ST Unit:UNIT 101 TUCSON, AZ 85719) TC-COM-0126-00047 (2333 E GLENN ST Unit:UNIT 201 TUCSON, AZ 85719) TC-COM-0126-00048 (2333 E GLENN ST Unit:UNIT 202 TUCSON, AZ 85719) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC). 1. Provide Surge Protection as required per 2023 NEC 230.67, NEC 230.67(D). 2. Note that the bottom of the conduits, over the roof of the buildings, shall be a minimum of 7/8” above the roof surface, NEC 310.15(B)(3)(c). Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||