Permit Number: TC-COM-0126-00010
Parcel: 109224440

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0126-00010
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2026 Commercial Building Standard APPROVED
01/16/2026 Commercial Electrical Standard APPROVED
01/28/2026 Commercial Plumbing Standard APPROVED
01/26/2026 Site Zoning Standard APPROVED
01/28/2026 Water - PDSD Standard APPROVED
01/14/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
01/09/2026 Site Engineering Standard NOT REQUIRED
01/28/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/28/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0126-00010
ADDRESS/PARCEL: 3636 N CRAYCROFT RD TUCSON, AZ 85718

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. The mechanical plan, M102, shows four high velocity diffusers (Titus 300FS, Double Deflection Grilles) located in close proximity to the face of the Type I hood. Verify that the location and type of air outlets complies with the hood manufacturer’s installation instructions and does not reduce the effectiveness of the exhaust system. Reference: Sections 304.1 and 508.1, IMC 2018.
01/27/2026 Fire New Construction Standard REVIEW COMPLETED
01/07/2026 PDSD Application Completeness Express REVIEW COMPLETED