Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0126-00006
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/06/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/06/2026 | Commercial Plumbing Express | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0126-00006 ADDRESS/PARCEL: (3701 E FAIRMOUNT ST TUCSON, AZ 85716) COMMENTS: 1. Please specify the type of gas piping being used (e.g., black iron, polyethylene, etc.) and indicate which sizing table from the 2024 IFGC you are referencing. Based on the information shown, the pipe size appears to be undersized. a. When looking at the gas line diagram, the total developed length appears to be 53 ft. Per Table 402.4(2) of the 2024 IFGC, the ¾-inch gas piping downstream of the water heater is undersized. With a combined demand of 165,000 BTUH for the range and furnace, this portion of the system would require 1-inch piping, assuming the line diagram is accurate. Please verify the total developed length, appliance loads, and pipe sizes, and ensure the gas piping system is properly sized to each appliance. |
||
| 01/05/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |