Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/20/2025 Commercial Building Standard REQUIRES RESUBMIT March 20, 2025
2nd Review

Seaver Franks Architects
Attn: Rick Huch/ Daren Sadowsky
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: STARR PASS MARRIOTT MARKETPLACE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0125-00209
Stantec Project Number: 185215066
Stantec File Number: TUC-25-023

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 I-B 3,600 N/A Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors and field welding.

GENERAL COMMENTS

1. New Comment: The plumbing set is missing sheet P1.0. The set was submitted with 2 copies of sheet P1.1 with one sheet being from the previous submittal and the other sheet is the revised version. Please resubmit the plan-set with sheet P1.0 and only the revised sheet P1.1.

ARCHITECTURAL COMMENTS

General

1. Addressed.

2. Addressed.

Sheet A0.0

1. Addressed.

Sheet A2.0

1. Addressed.

2. Addressed.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

Sheet E3.0

1. Addressed.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
03/20/2025 Commercial Electrical Standard REQUIRES RESUBMIT March 20, 2025
2nd Review

Seaver Franks Architects
Attn: Rick Huch/ Daren Sadowsky
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: STARR PASS MARRIOTT MARKETPLACE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0125-00209
Stantec Project Number: 185215066
Stantec File Number: TUC-25-023

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 I-B 3,600 N/A Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors and field welding.

GENERAL COMMENTS

1. New Comment: The plumbing set is missing sheet P1.0. The set was submitted with 2 copies of sheet P1.1 with one sheet being from the previous submittal and the other sheet is the revised version. Please resubmit the plan-set with sheet P1.0 and only the revised sheet P1.1.

ARCHITECTURAL COMMENTS

General

1. Addressed.

2. Addressed.

Sheet A0.0

1. Addressed.

Sheet A2.0

1. Addressed.

2. Addressed.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

Sheet E3.0

1. Addressed.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
03/20/2025 Commercial Mechanical Standard REQUIRES RESUBMIT March 20, 2025
2nd Review

Seaver Franks Architects
Attn: Rick Huch/ Daren Sadowsky
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: STARR PASS MARRIOTT MARKETPLACE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0125-00209
Stantec Project Number: 185215066
Stantec File Number: TUC-25-023

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 I-B 3,600 N/A Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors and field welding.

GENERAL COMMENTS

1. New Comment: The plumbing set is missing sheet P1.0. The set was submitted with 2 copies of sheet P1.1 with one sheet being from the previous submittal and the other sheet is the revised version. Please resubmit the plan-set with sheet P1.0 and only the revised sheet P1.1.

ARCHITECTURAL COMMENTS

General

1. Addressed.

2. Addressed.

Sheet A0.0

1. Addressed.

Sheet A2.0

1. Addressed.

2. Addressed.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

Sheet E3.0

1. Addressed.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
03/20/2025 Commercial Plumbing Standard REQUIRES RESUBMIT March 20, 2025
2nd Review

Seaver Franks Architects
Attn: Rick Huch/ Daren Sadowsky
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: STARR PASS MARRIOTT MARKETPLACE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0125-00209
Stantec Project Number: 185215066
Stantec File Number: TUC-25-023

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 I-B 3,600 N/A Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors and field welding.

GENERAL COMMENTS

1. New Comment: The plumbing set is missing sheet P1.0. The set was submitted with 2 copies of sheet P1.1 with one sheet being from the previous submittal and the other sheet is the revised version. Please resubmit the plan-set with sheet P1.0 and only the revised sheet P1.1.

ARCHITECTURAL COMMENTS

General

1. Addressed.

2. Addressed.

Sheet A0.0

1. Addressed.

Sheet A2.0

1. Addressed.

2. Addressed.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

Sheet E3.0

1. Addressed.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
03/17/2025 PDSD Application Completeness Express REVIEW COMPLETED